UPS Modular 480V 4W

Power Range: 60-720 kVA
| CIRRO
CIRRO UPS is AEC’s modular three-phase, double-conversion online UPS series, available in power ratings from 60 kVA to 720 kVA.
The UPS is designed for 480 V, three-phase, 5-wire (3Ph + N + G) systems.
The system is built on 60 kW hot-swappable power modules, installed in 360 kVA and 720 kVA frames, supporting scalable capacity expansion and N+X redundancy configurations.
This architecture allows incremental power growth and module replacement without load interruption, improving system availability and serviceability.
CIRRO operates with online double-conversion topology, delivering efficiency up to 96% and a unity (1.0) output power factor.
The system is equipped with a touchscreen display for monitoring, configuration, and diagnostics.
Three UPS levels
kW = kVA
96% Efficiency
TIER 1 UPS Highest efficiency
High-rate VRLA Batteries
8A Charger for fast recharge
Warranty
Assistance
Details


Gallery




Technical specifications
- UPS Model: CIR360-X60 | CIR720-X60
Input
- Voltage (VAC): 480Vac (L-L)
- Frequency (HZ): 40~70Hz
- Input range (VAC): 384-528VAC(L-L)@full load, 288-384VAC (L-L) power derate from 100% to 75%
- Power factory: ≥0.99
- THDI: ≤3%
- Phase: 3W+N+G
Output
- Power Module (kW): 60kVA
- Frame capacity (kW): 360kVA (Max 6 Modules x 60kVA) | 720kVA (Max 12 Modules x 60kVA)
- Power factor: 1
- Voltage (VAC): 480Vac (L-L)
- Frequency (HZ): 50/60±0.1
- THD: ≤1%THD, linear load; ≤5%THD, non-linear load
- Waveform: Pure sinewave
- AC/AC Efficency: 96,00%
- Overload: 110% 1 hour, 125%10 mins, 150% 1 min, >150% 200ms
Battery
- Voltage (VDC): Min ±180Vdc Max ±300Vdc settable by display
- Standard battery set: ±180Vdc
- Max. current Charger (A): 20% * UPS maximum capacity
Other specifications
- Recharging time: < 6 Hours
- Communications: Standard: RS232, E.P.O Contact and USB Port Optional: SNMP, Modbus, Dry contact
- Noise (DB): <50dB
- Temperature (°F – °C): 0°C – 40°C 32°F – 104°F
- Umidity: <95%
- Dimensions (W*D*H) in: 23.6*39.3*78.7 | 47.2*43.3*78.7
- Dimensions (W*D*H) cm: 60*100*200 cm | 120*110*200 cm
- Frame Weight (Lb – Kg): 546 Lb – 247 Kg | 1274 Lb – 578 Kg
- Power module (Lb – Kg): 90.4 Lb – 41 Kg
Certifications
- Standards: CE (IEC EN 62040-1; EMC IEC EN 62040-2; IEC EN 62040-3); UL1778
Advantages
Improved Voltage Control
A 3-level IGBT inverter introduces an intermediate voltage state (0 V), yielding three discrete levels: +Vdc, OV, and -Vdc.
Cleaner waveform
The staircase-shaped output more closely resembles a sine wave, reducing THD and interference.
Lower Harmonic Distortion (THD)
3 level IGBT reduces THD compared to the 2-level's rough waveform, improving power quality and reducing harmonic pollution.
Lower switching stress
Smaller voltage transitions mean each IGBT experiences less stress and switching loss, allowing for the use of lower-voltage, faster devices.
Higher efficiency
With reduced losses, heat dissipation and improved waveform quality, efficiency jumps above 96%, especially in new demanding critical power applications.
UPS Modular technology N+X
Modular UPS technology revolutionizes power protection by offering scalability, flexibility, and serviceability in a single solution. Unlike traditional monolithic systems, a modular UPS is composed of independent power modules that can be added, removed, or replaced without shutting down the system.
This architecture enables N+X redundancy, where “N” is the number of modules required to support the full load, and “X” represents additional modules for backup. For example, a 160 kW load can be protected by five 40 kW modules (N=4, X=1), ensuring continued operation even if one module fails.
Touch screen Smart Display
- Clear Display: A 10″ color touchscreen provides an easy and intuitive way to control the UPS.
- Secure Access: Three access levels (User, Technician, Manufacturer) protect system settings.
- Full Configuration: Adjust input, output, battery, communication, language, and operating modes directly from the screen.
- Live Monitoring: View real-time data like voltage, load, frequency, and battery status by cell at a glance.
- Event History: The UPS logs up to 10,000 events, downloadable via the built-in USB port.
- Generator Ready: Advanced settings ensure stable operation and communications with diesel generators.
- Custom Alarms: Set and manage dry contact alarms right from the touchscreen.
- Self-Cleaning: Automatic fan cycles help remove dust and keep internal parts clean.
- Waveform Display: The system periodically records inverter, rectifier, and control waveforms for diagnostics.
MODELS: CIR360-XX60 | CIR720-XX60
Found the right product?
Buy it now from our shop! Discover prices, availability, and configurations, and order in just a few clicks.
Download documentation
CIRRO 60-720k 480V Modular Catalog