Skip to content

UPS 3Phase 208V VRLA

Power Range: 10-30 kVA

| AUREON

The 208V three-phase Aureon UPS (10-30kVA) are double conversion tower UPS in powers 10kVA – 20kVA – 30kVA.
The UPS series adopts the most innovative 3-level IGBT technologies, ensuring efficiency up to 94% and a unitary output power factor.
UPS 208V 3 Phase Series incorporates cutting-edge features to ensure reliable and continuous power protection for critical electronic equipment.
One of its standout features is the internal Hot-swappable VRLA Lead Acid battery.

3 UPS levels

kW = kVA

94% Efficiency

TIER 1 UPS Highest efficiency

High-rate VRLA Batteries

More information

Download documentation

Cutting-Edge Technology

  • Utilizes IGBT and three-level technology for low harmonics and high efficiency
  • High power density design for space-saving installation
  • High input power factor and low Input THDi for reduced grid pollution and costs
  • AC/AC efficiency up to 94% to minimize power consumption costs
  • ECO mode efficiency up to 98.5% for significant cost reduction
  • Self-load test function for easy debugging and energy-saving
  • Wide DC voltage range for flexibility
  • Optimized installation and service architecture for easy maintenance

Frequency Converter

  • 50Hz-60Hz or 60Hz-50Hz converter mode
  • Possibility to disable the static bypass and DC power supply
  • Key components pre-alarm function for proactive maintenance.

MODELS: AUREON 10K-VRLA; AUREON 20K-VRLA; AUREON 30K-VRLA

Found the right product?

Buy it now from our shop! Discover prices, availability, and configurations, and order in just a few clicks.

Go to the shop

INPUT

  • VOLTAGE (VAC): 208/220 (3W+N+G)
  • FREQUENCY (HZ): 40~70
  • VOLTAGE BYPASS (VAC): 120-156 linear derating, 156V-268V at full load
  • POWER FACTOR: ≥0.99
  • THDI: ≤3%
  • PHASES: 3:3 Dual input

OUTPUT

  • POWER (KVA): 10 | 20 | 30
  • OUTPUT PERFORMANCE CLASSIFICATION (ACCORDING TO IEC 60240-3602): VFI-SS-111
  • POWER FACTOR: 1
  • VOLTAGE (VAC): 190/200/208±1%(L-L) ±1%
  • FREQUENCY (HZ): 50/60±0.1
  • THD: THD <1% (linear load), THD <4% (nonlinear load) WAVEFORM
  • WAVEFORM: Sinusoidal pure, THD<1% linear
  • EFFICIENCY: ACAC = 94%, ECO-Mode = 98,5%
  • OVERLOAD: <105% continues, 105%~110% 60mins, 110%~130% load for 10 min, 130%~150% load for 1 min, 150%~200% load for 200ms

VRLA BATTERIES

  • BATTERY CELL CAPACITY (AH): 9Ah
  • BATTERY PACK VOLTAGE (VDC): ±120 (±96 ~±120)
  • INTERNAL BATTERY STRING QUANTITY: Standard 2 strings (1-4 selectable) | Standard 3 strings (1-4 selectable) | Standard 4 strings (1-4 selectable)
  • CHARGING CURRENT (A): 1-10 settable | 1-20 settable

OTHER SPECIFICATIONS

  • COMMUNICATIONS: RS485+EPO+Dry contact (1 input, 5 output)+2 slots
  • DISPLAY: 4.3 Inches Touch Screen+ LED+ Physical buttons
  • ALARMS: Low batteries, Anormal input, Overload, Block/Fault ecc.
  • PROTECTIONS: Low batteries, Overload, Short-circuit, Over-temperature ecc.
  • NOISE (DB): <60 | <65
  • TEMPERATURE: -4°F~122°C
  • SAFETY REGULATORY: UL 1778, CSA C22.2 No.107.3-14 PERFORMANCE : IEC 60240-3
  • DIMENSIONS (W×D×H): 15×39×49 in / 378×993×1250 mm
  • PACKAGE DIMENSION (W×D×H): 18×43.7×54.7 in / 456×1110×1390 mm
  • WEIGHT WITHOUT BATTERIES: 456 lb/207 kg | 585 lb/270 kg | 734 lb/333 kg