UPS 3Phase 208V VRLA

Power Range: 10-30 kVA
| AUREON
The 208V three-phase Aureon UPS (10-30kVA) are double conversion tower UPS in powers 10kVA – 20kVA – 30kVA.
The UPS series adopts the most innovative 3-level IGBT technologies, ensuring efficiency up to 94% and a unitary output power factor.
UPS 208V 3 Phase Series incorporates cutting-edge features to ensure reliable and continuous power protection for critical electronic equipment.
One of its standout features is the internal Hot-swappable VRLA Lead Acid battery.
3 UPS levels
kW = kVA
94% Efficiency
TIER 1 UPS Highest efficiency
High-rate VRLA Batteries
Cutting-Edge Technology
- Utilizes IGBT and three-level technology for low harmonics and high efficiency
- High power density design for space-saving installation
- High input power factor and low Input THDi for reduced grid pollution and costs
- AC/AC efficiency up to 94% to minimize power consumption costs
- ECO mode efficiency up to 98.5% for significant cost reduction
- Self-load test function for easy debugging and energy-saving
- Wide DC voltage range for flexibility
- Optimized installation and service architecture for easy maintenance
Frequency Converter
- 50Hz-60Hz or 60Hz-50Hz converter mode
- Possibility to disable the static bypass and DC power supply
- Key components pre-alarm function for proactive maintenance.
MODELS: AUREON 10K-VRLA; AUREON 20K-VRLA; AUREON 30K-VRLA
Found the right product?
Buy it now from our shop! Discover prices, availability, and configurations, and order in just a few clicks.
INPUT
- VOLTAGE (VAC): 208/220 (3W+N+G)
- FREQUENCY (HZ): 40~70
- VOLTAGE BYPASS (VAC): 120-156 linear derating, 156V-268V at full load
- POWER FACTOR: ≥0.99
- THDI: ≤3%
- PHASES: 3:3 Dual input
OUTPUT
- POWER (KVA): 10 | 20 | 30
- OUTPUT PERFORMANCE CLASSIFICATION (ACCORDING TO IEC 60240-3602): VFI-SS-111
- POWER FACTOR: 1
- VOLTAGE (VAC): 190/200/208±1%(L-L) ±1%
- FREQUENCY (HZ): 50/60±0.1
- THD: THD <1% (linear load), THD <4% (nonlinear load) WAVEFORM
- WAVEFORM: Sinusoidal pure, THD<1% linear
- EFFICIENCY: ACAC = 94%, ECO-Mode = 98,5%
- OVERLOAD: <105% continues, 105%~110% 60mins, 110%~130% load for 10 min, 130%~150% load for 1 min, 150%~200% load for 200ms
VRLA BATTERIES
- BATTERY CELL CAPACITY (AH): 9Ah
- BATTERY PACK VOLTAGE (VDC): ±120 (±96 ~±120)
- INTERNAL BATTERY STRING QUANTITY: Standard 2 strings (1-4 selectable) | Standard 3 strings (1-4 selectable) | Standard 4 strings (1-4 selectable)
- CHARGING CURRENT (A): 1-10 settable | 1-20 settable
OTHER SPECIFICATIONS
- COMMUNICATIONS: RS485+EPO+Dry contact (1 input, 5 output)+2 slots
- DISPLAY: 4.3 Inches Touch Screen+ LED+ Physical buttons
- ALARMS: Low batteries, Anormal input, Overload, Block/Fault ecc.
- PROTECTIONS: Low batteries, Overload, Short-circuit, Over-temperature ecc.
- NOISE (DB): <60 | <65
- TEMPERATURE: -4°F~122°C
- SAFETY REGULATORY: UL 1778, CSA C22.2 No.107.3-14 PERFORMANCE : IEC 60240-3
- DIMENSIONS (W×D×H): 15×39×49 in / 378×993×1250 mm
- PACKAGE DIMENSION (W×D×H): 18×43.7×54.7 in / 456×1110×1390 mm
- WEIGHT WITHOUT BATTERIES: 456 lb/207 kg | 585 lb/270 kg | 734 lb/333 kg
Download documentation
Aureon UPS Catalog